Model Number |
LW49-75KV/126KV Outdoor HV AC SF6 Circuit Breaker |
Detailed Selling Lead Description
Product overview
LW49-126 Outdoor HV AC Self Extinguishing SF6 Circuit Breaker is used in the electrical system of 3-phase AC 50Hz,110 KV, as its control and protective equipment, and also a connecting circuit breaker for switching loading current, cutting-off fault current and switching over power circuit through various wiring ways in the power plant and substation.
Product standard
This circuit breaker is compliant with GB1984-2003 HV AC Circuit Breaker and IEC 56 HV AC Circuit Breaker .It is insulated and arc-extinguished by SF6, complying with self-extinguishing principle. Working with the spring actuator, it has the following features: powerful breaking capability, long electric life of 20 times, lower active power, and high reliability.
Strong ability of breaking, CB uses self-extinguishing principle, with high breaking and closing ability. Whole annul leak rating<0.02%( O ring uses Sino-America joint company PAK company, the mould and material made in America)
Micro moisture of arc extinguishing chamber <100ppmV/V
Micro moisture of other chambers <150ppm V/V
Technical parameter
|
Serial no
|
Item
|
Unit
|
Data
|
|
1
|
Rated voltage
|
KV
|
75/126
|
|
2
|
Rated frequency
|
Hz
|
50
|
|
3
|
Rated current
|
A
|
3150
|
|
4
|
Rated short-circuit breaking current
|
kA
|
40
|
|
5
|
Rated short-circuit makeup current (peak)
|
kA
|
100
|
|
6
|
Rated peak withstand current
|
kA
|
100
|
|
7
|
Rated short-time withstand current
|
kA
|
40
|
|
8
|
Rated short-circuit duration
|
s
|
4
|
|
9
|
Electrical life
|
times
|
20
|
|
10
|
Rated power frequency withstand voltage
|
Over earth, between phases
|
kV
|
230
|
|
Between fractures
|
kV
|
265
|
|
11
|
Rated lightning pulse withstand voltage
|
Over earth,between phses
|
kV
|
550
|
|
Between fractures
|
kV
|
630
|
|
12
|
Rated out-of-step breaking current
|
kA
|
10
|
|
13
|
Rated circuit charging breaking current
|
A
|
31.5
|
|
14
|
Near-field fault breaking current
|
kA
|
36.30
|
|
15
|
Main loop resistance
|
µΩ
|
40
|
|
16
|
Mechanical life
|
times
|
10000
|
|
17
|
Rated pressure of SF6 (Guage at 20)
|
Mpa
|
0.6
|
|
18
|
Alarming purssure of SF6 (Guage at 20)
|
Mpa
|
0.55
|
|
19
|
Locking purssure of SF6 (Guage at 20)
|
Mpa
|
0.5
|
|
20
|
Creepage distance
|
mm
|
3150,3906
|
|
21
|
Rated operation squence
|
|
0-0.3s-CO-180s-CO
|
|
22
|
Radio interference level
|
µ V
|
500
|
|
23
|
Yearly leakage rate of SF6
|
%
|
1%
|
|
24
|
Water content of SF6
|
Ppm
|
150
|
|
25
|
Mass of SF6 for each circuit breaker
|
Kg
|
10
|
|
26
|
Mass of each circuit breaker
|
Kg
|
1800
|
|
27
|
Break-break force (downward)
|
N
|
25000
|
|
28
|
Close-brake force (upward)
|
N
|
15000
|
|