Beijng Huadong Electric Co.,Ltd
|
|
| |
| Products |
|
 |
HC AC Self-extinguishing SF6 Circuit Breaker |
|
|
|

|

|
Click to enlarge image
|
Model Number |
126KV/145KV outdoor HV AC SF6 Circuit breaker |
126KV/145KV outdoor HV AC Self Extinguishing SF6 Circuit Breaker
Product overview
Outdoor HV AC Self Extinguishing SF6 Circuit Breaker is used in the electrical system of 3 phase AC 50Hz,132kV /145kV as its control and protective equipment, and also a connecting circuit breaker for switching loading current, cutting off fault current and switching over power circuit through various wiring ways in the power plant and substation.
Product standard
This circuit breaker is compliant with GB 1984-2003 HV Circuit Breaker and IEC 56 HV AC Circuit Breaker. It is insulated and arc-extinguished by SF6, complying with self extinguishing principle. Working with the spring actuator, it has the following features: powerful breaking capability, long electric life of 20 times, lower active power and high reliability.
Technical parameter
|
Serial no
|
Item
|
Unit
|
Data
|
|
1
|
Rated voltage
|
KV
|
132/145
|
|
2
|
Rated frequency
|
Hz
|
50
|
|
3
|
Rated current
|
A
|
3150
|
|
4
|
Rated short-circuit breaking current
|
kA
|
40
|
|
5
|
Rated short-circuit makeup current (peak)
|
kA
|
100
|
|
6
|
Rated peak withstand current
|
kA
|
100
|
|
7
|
Rated short-time withstand current
|
kA
|
40
|
|
8
|
Rated short-circuit duration
|
s
|
4
|
|
9
|
Electrical life
|
times
|
20
|
|
10
|
Rated power frequency withstand voltage
|
Over earth, between phases
|
kV
|
245
|
|
Between fractures
|
kV
|
315
|
|
11
|
Rated lightning pulse withstand voltage
|
Over earth,between phses
|
kV
|
650
|
|
Between fractures
|
kV
|
750
|
|
12
|
Rated out-of-step breaking current
|
kA
|
10
|
|
13
|
Rated circuit charging breaking current
|
A
|
31.5
|
|
14
|
Near-field fault breaking current
|
kA
|
36.30
|
|
15
|
Main loop resistance
|
µΩ
|
40
|
|
16
|
Mechanical life
|
times
|
10000
|
|
17
|
Rated pressure of SF6 (Guage at 20)
|
Mpa
|
0.6
|
|
18
|
Alarming purssure of SF6 (Guage at 20)
|
Mpa
|
0.55
|
|
19
|
Locking purssure of SF6 (Guage at 20)
|
Mpa
|
0.5
|
|
20
|
Creepage distance
|
mm
|
3625
|
|
21
|
Rated operation squence
|
|
0-0.3s-CO-180s-CO
|
|
22
|
Radio interference level
|
µ V
|
500
|
|
23
|
Yearly leakage rate of SF6
|
%
|
1%
|
|
24
|
Water content of SF6
|
Ppm
|
150
|
|
25
|
Mass of SF6 for each circuit breaker
|
Kg
|
10
|
|
26
|
Mass of each circuit breaker
|
Kg
|
2000
|
|
27
|
Break-break force (downward)
|
N
|
25000
|
|
28
|
Close-brake force (upward)
|
N
|
15000
|
|
|
|
|
| |
|
|
|