Item
|
parameter
|
|
Rated voltage kV
|
252
|
|
Rated frequency Hz
|
50
|
|
Rated current A
|
3150
|
|
Rated short-circuit breaking current kA
|
50
|
|
Rated short-circuit makeup current (peak) kA
|
125
|
|
Rated short-time withstand current kA
|
50
|
|
Rated short-circuit duration S
|
2, (3)
|
|
Rated peak withstand current kA
|
125
|
|
Near-field fault breaking current L75 L90 kA
|
37.5/45
|
|
Rated phase-out makeup and breaking current kA
|
12.5
|
|
Rated circuit charge breaking current A
|
160
|
|
insulation level
|
1min rated power-frequency withstand voltage kV (virtual value)
|
over ground
|
460
|
|
between fracture
|
395+145
|
|
Rated lightning impulse withstand voltage(1.2/50µs) kV (peak)
|
over ground
|
1050
|
|
between fracture
|
950+206
|
|
Rated pull in terminal N
|
level vertical
|
1500
|
|
level horizontal
|
1000
|
|
vertical direction
|
1250
|
|
Creepage distance mm
|
6300, 7812
|
|
Rated operation sequence
|
O-0.3s-CO-180s-CO
|
|
Gas rated pressure of SF6 (20) MPa
|
0.6
|
|
Leak rate of SF6 per year ≤ %
|
1
|
|
Moisture content of SF6 gas ≤ µ L/L
|
150
|
|
Continuous breaking times of rated short-circuit breaking current times
|
20
|
|
Mechanical operation times times
|
3000
|
|
Break-brake time ms
|
18~25
|
|
Close-brake time ms
|
80~100
|
|
Break and close time ≤ ms
|
0.3
|
|
Close and break time ≤ ms
|
60
|
|
Asynchronism of anode-to-cathode break brake
≤ ms
|
3
|
|
Asynchronism of anode-to-cathode close brake
≤ ms
|
5
|
|
Monopole gas weight of SF6 kg
|
46
|